Overview
RO-PRO controllers are the complete solution to yourautomated RO plant.This controller controls the Raw water pump,High Pressure pump,Dosing Pump,Pump and Flushing Solenoid. It also has a hooterto indicate alarms.The controller also takes in inputs from key sensors like LPswitch, HP switch Conductivity controllers, pH controllers,ORP Controllers,Inlet switch, Product level switch, Dosing level and switch more. The controller also continuously monitors phase voltages currents, phase phase reversal and imbalances. This ensures that your plant trips for unbalanced voltages orexcessive currents. Further these controllers can talk to ourMotorized Multiport Valves over a RS485 connectionto control these valves. RO-PRO can also differentiate between permanent alarms and temporary alarms.
Phase Voltage / Current Monitoring / Trip
Single Phase Prevention
Controls multiple Motorized valves over a simple 2 wire RS485
8 / 16(Optional) Digital Inputs
16 Chr. 2 Line Backlit LCD Display
Programmable Trip Points
19 LED’s for process indication
Automates LP, HP, Cleaning, Flushing
RS485 connectivity
96x96 Panel Mount Enclosure
Specification |
||
|---|---|---|
| Indication | : | 16 Character 2 Line Backlit LDD Display |
| Indication Parameter | : | Phase Voltages, Phase Currents, |
| Frequency, Last Time Run, Current Plant | ||
| Run Time, Trip Parameters, Time in | ||
| current StateState and Conductivity | ||
| Alaram | : | Low Pressure, High Pressure, High/Low |
| Voltage / Current, Phase Sequence, | ||
| Dosing Low, InletLow/High, Product | ||
| Low/High, Conductivity/pH/ORP and | ||
| optional additional 8 digital inputst | ||
| Programming | : | Using 6 keys in the front pane |
| Indiacation Accuracy | : | +- 2% of full scale |
| Operating Temperature | : | -0 to 50 Deg C |
| Storage Temperature | : | -40 to 85 Deg C |
| Humidity | : | 5-90% RH non-condensing |
| Relay Output | : | 3 Standard, 6 Maximum |
| ;Relay Contact Rating | : | 5A, 220V AC Maximum |
| Housing | : | ABS face with MS Powder coated rear |
Power Requirement |
||
| Voltage | : | 220VAC +-15% or 8 to 24VAC/DC (Factory Settable) |
| Frequency | : | 50/60 Hz |
| Power Consuption | : | Less than 2 Watt |
Optional Feature |
||
| Conductivity | : | RS485, MODBUS protocol |
| HP Output Rating | : | 2 (4-20mA / 0-5V) inputs |