Overview
AC200 is controller for water cooled air conditioners. This instrument monitors the conductivity of water. The water is flushed out when the conductivity crosses a specified set point. This instrument has 4 digit LED display and two keys for programming. Programmable relay outputs for water flushing and fill controlling. AC200 continuously monitors compressor ON time. Water flushing time can be programmed by user. AC200 flushes out the water based on conductivity or time or both (programmable in the instrument.AC200 monitors temperature , water level and conductivity and displays each parameter in the LED display.
| Four Digit LEDs | |
| Field programmable through two keys | |
| Conductivity Display with Temperature Compensation | |
| Temperature of cooling water display | |
| Total Hours Run Display | |
| Time Left for flushing display | |
| Air conditioner state, time remaining in state and time in state display | |
| Water Level Low Input | |
| Relay Output for Fan/Circulation pump control | |
| Relay Output for Flushing pump |
| Specification | ||
|---|---|---|
| Power Supply | : | 200V to 230V AC |
| Power Consumption | : | Less than 1 Watt |
| Indication | : | 4 Digit 7 Segment LED display |
| Indicated Parameters | : | Conductivity, Temperature, Time Left for Flushing, Total Hours Run, Controller state (with time left in current state or time in state) |
| Alarms | : | Water Level Low |
| Programming | : | Using 2 keys |
| Indication Accuracy | : | ±2.5% of scale |
| Programmable Parameters | : | Refer to section on Programming |
| Operating Temperature | : | 0 – 50 °C |
| Storage Temperature | : | 0 – 70 °C |
| Humidity | : | 5 – 90 % RH non-condensing |
| Relay Outputs | : | 2 Relays. All relays rated for 220V AC 7A maximum. Derate relays by 25% for inductive loads |
| Board Size | : | 13.4 cm x 6.7cm |